Inspection #: 586636
Inspection Type: Electrical Rough
Inspector: M.Green
Result: Partial
Comment: Ten unit meters approved. Tags #35638 - #35647. Items below will need to be resolved before final.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
11/5/2019Transfer01See inspection comments Bonding connection from service to building steel.Required to be accessible. Does not qualify for exception at 250.68(A) Exception #2.
11/5/2019Transfer01See inspection comments Feeder gutters behind service.Equipment grounds required to bond to gutters.
11/5/2019Transfer01See inspection comments Service, (2) panels closest to service.DWGS show AFC at service as 42K+, and AFC at (2) closest panels as 12K and 15K. Service main breaker rated at 65KAIC; all feeder breakers and branch circuit breakers rated 10KAIC. Need to show series rating. Will need proper series rating labelling.