| Date | Status | Code | Description | Ref | Location | Comments |
| 11/5/2019 | Transfer | 01 | See inspection comments | | Bonding connection from service to building steel. | Required to be accessible. Does not qualify for exception at 250.68(A) Exception #2. |
| 11/5/2019 | Transfer | 01 | See inspection comments | | Feeder gutters behind service. | Equipment grounds required to bond to gutters. |
| 11/5/2019 | Transfer | 01 | See inspection comments | | Service, (2) panels closest to service. | DWGS show AFC at service as 42K+, and AFC at (2) closest panels as 12K and 15K. Service main breaker rated at 65KAIC; all feeder breakers and branch circuit breakers rated 10KAIC. Need to show series rating. Will need proper series rating labelling. |