Inspection #: 584212
Inspection Type: Plumbing Rough
Inspector: J.Jaworski
Result: Correction
Comment: Call for reinspection, see corrections

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/1/2019TransferPlumbRgh14CommentsSee Inspectors CommentsWater piping on strutdissimilar metals require protection, example; 10 mil tape. 312.4 2012 UPC
10/1/2019TransferPlumbRgh14CommentsSee Inspectors CommentsABS piping overhead, water piping in closetPressure test required
10/1/2019TransferPlumbRgh12Piping SupportPiping is not properly supported- UPC Section 313.0, including Table 313.1ABS piping throughout, vertical risers are not support 