Inspection #: 581664
Inspection Type: Fire Alarm Final
Inspector: C.Mondloch
Result: Approved
Comment: Please give me a heads up, as I am not on site. Thank you Requested by: Clinton Justus 9072024573 cj@g2const.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
8/21/2019CorrectedFireWalarmFinalOtherFire Alarm Final OtherPlease correct the following: Elevator is recalling to the correct floors upon smoke detector activation.  Make the following corrections: (1) smoke detector activation on the 1st floor, 2nd floor and elevator machine room shall recall the elevator to the 3rd floor  (2) smoke detector activation on the 3rd floor shall recall the elevator to the 1st floor.   Curt Burgoyne (MOA Elevator Inspector) was on site on 8/21/2019 with Bart Meinhardt (Fire Inspector).
8/21/2019Correctedfirealarm13Please correct the followingPlease correct the following: (1) Separate signal shall report to Guardian security for CO alarm.  It shall report as a supervisory to the fire alarm panel, Guardian shall receive it as a CO alarm.  (2) Dinning room relocate ceiling strobe to cover as a 95 cd or add strobe.  (3) Remove all old devices throughout facility (Boiler room has existing).   