Date | Status | Code | Description | Ref | Location | Comments |
8/21/2019 | Corrected | FireWalarmFinalOther | Fire Alarm Final Other | Please correct the following: | | Elevator is recalling to the correct floors upon smoke detector activation. Make the following corrections: (1) smoke detector activation on the 1st floor, 2nd floor and elevator machine room shall recall the elevator to the 3rd floor (2) smoke detector activation on the 3rd floor shall recall the elevator to the 1st floor. Curt Burgoyne (MOA Elevator Inspector) was on site on 8/21/2019 with Bart Meinhardt (Fire Inspector). |
8/21/2019 | Corrected | firealarm13 | Please correct the following | Please correct the following: | | (1) Separate signal shall report to Guardian security for CO alarm. It shall report as a supervisory to the fire alarm panel, Guardian shall receive it as a CO alarm. (2) Dinning room relocate ceiling strobe to cover as a 95 cd or add strobe. (3) Remove all old devices throughout facility (Boiler room has existing). |