Inspection #: 580927
Inspection Type: Electrical Rough
Inspector: E.Widman
Result: Correction
Comment: See corrections.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
9/9/2019Transfer01See inspection comments  Conduit seals not inspected prior to pouring. What type of sealing system/compound was used?
9/9/2019Transfer01See inspection comments Conduit/raceways to hazardous/classified locations. Area wired as hazardous location. Bonding for wiring to classified location required to comply with 250.100 and 501.30 of NEC.
9/9/2019Transfer01See inspection comments Veeder-root panelDoes alarm panel associated with veeder-root system have overall listing for control panel. Appears to be a listed enclosure, but not a listed control panel. Factory provided Wiring diagram required for units (veeder-root and remote alarm panel). Is remote alarm panel connected to veeder-root part of overall listing of veeder-root system? Provide documentation showing associated equipment.
9/9/2019Transfer01See inspection comments Provide data sheet for paddle lugs to be used for grounding and bonding of equipment. Required to be suitable for use.  
9/9/2019Transfer01See inspection comments Low volt cable at tank. Is cable a type with exterior jacket impervious to gasses? Provide documentation.
9/9/2019Transfer01See inspection comments Day and main tank associated with project. Area not shown on plans as hazardous/classified location. Area at tanks wired as hazardous/classified area. Document classified area on plans (reference 500.4). Required to verify location of classified location to verify proper placement of boundary seals.
9/9/2019Transfer01See inspection comments Is this an NEC article 700,701,702 or 708 type system related to the function of airport facilities? Document on plans if so.  
9/9/2019Transfer01See inspection comments Underground for grounding and bonding/ground ring covered without inspection.  
9/9/2019Transfer01See inspection comments Low volt wiring at main tank. Are these circuits intrinsically safe or nonincendive circuits? labels required per 504.80.