| Date | Status | Code | Description | Ref | Location | Comments |
| 9/4/2019 | Transfer | Correct Below | * | | Lighting. | DWGS show (2) lighting circuits. All lighting connected to (1) circuit. |
| 9/4/2019 | Transfer | Correct Below | * | | DWGS show troffers with battery back-up EM ballasts. | Bug eye" style EM lights installed instead.
Verify EM lights not on multi-wire branch circuits.
Engineer needs to approve. |
| 9/4/2019 | Transfer | Correct Below | * | | Main dental operating area, station TR#5. | Dental equipment not being installed.
Engineer needs to revise DWG to show actual installation. |
| 9/4/2019 | Transfer | Correct Below | * | | Main dental operating area. | DWGS show power to all dental beds / chairs. Chairs not powered.
Engineer needs to revise DWG to show installation as is. |
| 9/4/2019 | Transfer | Correct Below | * | | Med. gas closet. | 120V transformer to power low voltage med. gas controls; is this listed? |
| 9/4/2019 | Transfer | Correct Below | * | | Med. gas closet. | Is this a hazardous location? Sign on door instructs to ventilate before entering and no smoking, etc. |
| 9/4/2019 | Transfer | Correct Below | * | | Coffee room 111 refrigerator receptacle. | Within 6 feet of sink requires GFCI protection. |
| 9/4/2019 | Transfer | Correct Below | * | | Room 113 and main dental operating area. | Proma" dental light not connected to power. Other areas: TV monitors not installed |
| 9/4/2019 | Transfer | Correct Below | * | | Planmeca X-ray machine. | Show instructions permitting hardwired cord connection. |
| 9/4/2019 | Transfer | Correct Below | * | | Various. | 2017 NEC 406.12(5) requires tamper resistant receptacles in "...business offices, corridors, waiting rooms, and the like..." in dental offices. |