Inspection #: 580701
Inspection Type: Final Electrical
Inspector: M.Green
Result: Correction
Comment: Please Call 30 min Prior Requested by: Jaimey Sapp 9072292269 northerntechsolutions@gmail.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
9/4/2019TransferCorrect Below* Lighting.DWGS show (2) lighting circuits. All lighting connected to (1) circuit.
9/4/2019TransferCorrect Below* DWGS show troffers with battery back-up EM ballasts.Bug eye" style EM lights installed instead. Verify EM lights not on multi-wire branch circuits. Engineer needs to approve.
9/4/2019TransferCorrect Below* Main dental operating area, station TR#5.Dental equipment not being installed. Engineer needs to revise DWG to show actual installation.
9/4/2019TransferCorrect Below* Main dental operating area.DWGS show power to all dental beds / chairs. Chairs not powered. Engineer needs to revise DWG to show installation as is.
9/4/2019TransferCorrect Below* Med. gas closet.120V transformer to power low voltage med. gas controls; is this listed?
9/4/2019TransferCorrect Below* Med. gas closet.Is this a hazardous location? Sign on door instructs to ventilate before entering and no smoking, etc.
9/4/2019TransferCorrect Below* Coffee room 111 refrigerator receptacle.Within 6 feet of sink requires GFCI protection.
9/4/2019TransferCorrect Below* Room 113 and main dental operating area.Proma" dental light not connected to power. Other areas: TV monitors not installed
9/4/2019TransferCorrect Below* Planmeca X-ray machine.Show instructions permitting hardwired cord connection.
9/4/2019TransferCorrect Below* Various.2017 NEC 406.12(5) requires tamper resistant receptacles in "...business offices, corridors, waiting rooms, and the like..." in dental offices.