Inspection #: 580270
Inspection Type: Electrical Rough
Inspector: M.Green
Result: Partial
Comment: Requested by: Curtis 748-4916 cb@sei-ak.com Various conduit stub-outs through the foundation, west end. #2 CU GEC connected to grade beam rebar and to driven steel piling under grade beam. Approved. NOTE: Building service will be 600A. Building steel will connect to driven pilings for exterior canopy using #2/0 CU.