Inspection #: 579973
Inspection Type: Fire Alarm Final
Inspector: B.Meinhardt
Result: Partial
Comment: This will be a after hrs. Inspection. Bart M. Is aware Requested by: Tennes Tenneson 9079806226 Criteriongeneral@conocophillips.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/14/2019Transferfirealarm11Fire Alarm approved CCOFire Alarm approved for CCO Fire alarm approved for CCO till Nov 15 2019
10/14/2019Transferfirealarm13Please correct the followingPlease correct the following: (1) 11th floor has horn strobe installed and needs strobe only installed in the ceiling (2) Submit change order to show relocated devices, deletions and strobe candla changes on the 11th and 12th floors.  (3) Submit as built plans to plan set in fire command center and building main file