Inspection #: 579670
Inspection Type: Final Plumbing
Inspector: J.Jaworski
Result: Partial
Comment: Rest of plumbing final APPROVED, FIRST PORTION OF 24 HOUR STANDING PRESSURE TEST OF 1 EA. ADDITIONAL INLET/OUTLET, VAC AND O2 @ #150 OK FOR CCO FROM 10-2-19 THROUGH 11-2-19, NEW OUTLETS NOT TO BE USED UNTIL 3RD PARTY VERIFICATION

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/2/2019TransferPlumbFinalCommentsSee Inspector Comments CHANGER ORDER REQUIRED. ENGINEER ON RECORD TO FILL OUT FORM FOR FIELD INSPECTOR. DOES NOT REQUIRE PLAN REVIEW, FILL OUT FORM FOR FIELD INSPECTOR. https://www.muni.org/Departments/OCPD/development/BSD/Forms/FIELDCHANGEORDERREQUEST012312.pdf
8/27/2019CorrectedPlumbFinalCommentsSee Inspector Comments MRI to be onsite and verify it meets muni requirements for cooling appliances.
8/27/2019CorrectedPlumbFinalCommentsSee Inspector Comments 3RD PARTY VERIFICATION APPROVAL REQUIRED