Inspection #: 574657
Inspection Type: Final Fire Inspection
Inspector: C.Mondloch
Result: CondAppr
Comment: Call TC at 980-6226 prior to inspection Requested by: TC Tenneson 907-980-6226 jeffm@criteriongeneral.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
7/30/2019 FireOtherOtherCorrection(s) #1Please correct the following item(s): <p>CCO approved for 30 days (expires 08/30/19)&nbsp; </p><p>Install certification for sprinkler system received by the municipality.</p><p>Install certification for upgrade work to fire alarm system for 11th and 12th floor received by the municipality as well, however, A permit will need to be issued for fire alarm and plans will need to be submitted, reviewed and system witnessed prior to issuance of CO per the previous comments from prior inspection.</p>
7/26/2019 Fire 13Correction(s) #1Please correct the following: 1) New ceiling tile installed required over sized escutcheons on hard piped sprinkler heads (2) Fire alarm permit required - changes to a networked fire alarm system 23.45 Appendix K K103.4 #4b.&nbsp; System is voice EVAC and requires voice intelligibility.&nbsp; Design and testing shall be approved and witnessed by AFD. (3) Need to check emergency door release.&nbsp; (4) NOPR issued for Criterion General and Laker Electric.