Inspection #: 571471
Inspection Type: Final Electrical
Inspector: E.Widman
Result: Correction
Comment: See corrections. Correction for GFCI protection for gate opener service receptacle remains.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
7/9/2019 Correct Below* GateProvide Readily accessible GFCI protection for gate service receptacle.
7/9/2019TransferCorrect Below* Lift station. No access to verify. Is boundary seal provided between tank and room (C1D2 and non classified area)? Provide documentation if cables are type with gas/vapor tight sheath and that assembly is incapable of transmitting gasses to unclassified area. Plan notes require boundary seal at tank. Reference 501.15 (B) and (E) for conduit and cable.
7/9/2019TransferCorrect Below* Lift station. No access provided to pump to verify Overload protection. Is overload protection provided for pump? Size overload protection. Noted on wiring diagram as well. Size per 430.32.
7/9/2019TransferCorrect Below* Lift station control panel.Literature notes max overcurrent protection 15 amp.
7/9/2019TransferCorrect Below* Lift station.Post documentation of classified location at lift station area. Required to be available for inspection, installation, and maintenance.