| Date | Status | Code | Description | Ref | Location | Comments |
| 7/9/2019 | | Correct Below | * | | Gate | Provide Readily accessible GFCI protection for gate service receptacle. |
| 7/9/2019 | Transfer | Correct Below | * | | Lift station. | No access to verify. Is boundary seal provided between tank and room (C1D2 and non classified area)? Provide documentation if cables are type with gas/vapor tight sheath and that assembly is incapable of transmitting gasses to unclassified area. Plan notes require boundary seal at tank. Reference 501.15 (B) and (E) for conduit and cable. |
| 7/9/2019 | Transfer | Correct Below | * | | Lift station. No access provided to pump to verify Overload protection. | Is overload protection provided for pump? Size overload protection. Noted on wiring diagram as well. Size per 430.32. |
| 7/9/2019 | Transfer | Correct Below | * | | Lift station control panel. | Literature notes max overcurrent protection 15 amp. |
| 7/9/2019 | Transfer | Correct Below | * | | Lift station. | Post documentation of classified location at lift station area. Required to be available for inspection, installation, and maintenance. |