| Date | Status | Code | Description | Ref | Location | Comments |
| 7/1/2019 | Transfer | Fire 13 | Correction(s) #1 | Please correct the following: | | (1) Provide fire extinguishers in each unit and mechanical room - Minimum size 5 pound ABC 2A:40BC (2) Provide 4 bollards in front of each set of gas meters in compliance with 2012 International Fire Code Section 312. (3) Provide on the building a KnoxBox 10 key box - Call 267-4950 to schedule a fire truck. (4) Install sign on mechanical room "Fire Sprinkler Room" 2 inch white letter on red back ground. (5) Complete sprinkler repairs on replacing all painted heads in bathrooms (6) complete fire sprinkler and fire alarm issues. |