Inspection #: 570368
Inspection Type: Final Fire Inspection
Inspector: B.Meinhardt
Result: Correction
Comment:

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
7/1/2019TransferFire 13Correction(s) #1Please correct the following: (1) Provide fire extinguishers in each unit and mechanical room - Minimum size 5 pound ABC 2A:40BC (2) Provide 4 bollards in front of each set of gas meters in compliance with 2012 International Fire Code Section 312. (3) Provide on the building a KnoxBox 10 key box - Call 267-4950 to schedule a fire truck.  (4) Install sign on mechanical room "Fire Sprinkler Room" 2 inch white letter on red back ground.  (5) Complete sprinkler repairs on replacing all painted heads in bathrooms (6) complete fire sprinkler and fire alarm issues.