Inspection #: 570048
Inspection Type: Electrical Rough
Inspector: D.Rooney
Result: Correction
Comment: Corrections required

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
6/27/2019Transfer01See inspection comments at panelcircuits involved in this remodel must have dedicated neutrals or have a handle-ties installed
6/27/2019Transfer01See inspection comments at track lightsseismic support wires required for track lights
6/27/2019Transfer01See inspection comments above check out counteropen boxes need covers, MC cable to power pole not supported within 12" of box, existing 1/2" flex between J-boxes not properly supported and box needs a cover
6/27/2019Transfer01See inspection comments at check out counterneed to verify that ground to IG receptacles is isolated