Inspection #: 568257
Inspection Type: Fire Sprinkler Rough-In
Inspector: M.Warren
Result: CondAppr
Comment: Test is for Rough-In and Hydro Test. Please call one hour in advance. Schedule with F18-1279. Requested by: Yoni Garcia-Velasco 907-414-8386 Yoni@taylorfire.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
6/17/2019 FireSprnkRoughOtherFire Sprinkler Rough Partial ApprovalFire Sprinkler Rough Partial Approval.   List area(s) approved Rough in and hydro partial approval, Provide additional 2 way brace at FDC turn and provide 2 inches clearance around riser.