Inspection #: 566913
Inspection Type: Final Electrical
Inspector: D.Rooney
Result: Partial
Comment: Conditional electrical final approved until 6/21/2019

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
6/7/2019TransferCorrect Below* KEF-1 In south panelKEF-1 still on 20 amp circuit (should be 15 amp) - panel schedule appears incorrect (KEF-1 shown as circuitt 24 which is a 2-pole breaker appears to be MAU unit - circuits 22 through 26 appears shifted
6/7/2019TransferCorrect Below* heat trace circuit in south panellock-out device required for heat trace circuit