Inspection #: 565536
Inspection Type: Framing / Int.
Inspector: H.Kahlstrom
Result: Correction
Comment:

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
6/7/2019TransferINTFRAMEBInterior framing correctionComplete the following correctionsRoom 1225Detail 02/A401 describes walls at this area as continuing to structure not terminating at the drywall hard lid. Extend walls to structure per plan.
6/7/2019TransferINTFRAMEBInterior framing correctionComplete the following corrections12th floor T.I.Rm 1200 Provide box header at openings over 48" (large relite 10'-0")
5/29/2019TransferINTFRAMEBInterior framing correctionComplete the following corrections11th floor tenant improvement1) Provide lateral restraint at top of wall not extending to structure as required. 2) Replace SFPM at WF steel beams where removed or damaged by earthquake. 3) Firestop core drilled floor penetration at break area waste line.