| Date | Status | Code | Description | Ref | Location | Comments |
| 5/31/2019 | Transfer | firealarm13 | Please correct the following | Please correct the following: | | (1) Building on wrong address, actual address is 2751 Debarr, need to fix permit (2) Strobe locations have changes, candela is to low (3) Horn strobes do not have synchronization (4) Strobes are flashing to slow and do not comply with 18.5.2.1 (5) add strobe in hall by bathroom (6) Smoke detector required over BPS (7) Strobes are mounted to low at 79 inch, required to be 80" to 96" - 2010 NFPA 72 section 18.5.4.1 (8) get change order for fire alarm changes. |