Inspection #: 564651
Inspection Type: Final Fire Inspection
Inspector: B.Meinhardt
Result: Correction
Comment: Call TC prior to inspection at 980 - 6226 Requested by: TC Tenneson 980-6226 jeffm@criteriongeneral.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
7/26/2019TransferFire 13Correction(s) #1Please correct the following: 1) New ceiling tile installed required over sized escutcheons on hard piped sprinkler heads (2) Fire alarm permit required - changes to a networked fire alarm system 23.45 Appendix K K103.4 #4b.  System is voice EVAC and requires voice intelligibility.  Design and testing shall be approved and witnessed by AFD. (3) Need to check emergency door release.  (4) NOPR issued for Criterion General and Laker Electric.