Inspection #: 564531
Inspection Type: Electrical Inspection
Inspector: E.Widman
Result: Correction
Comment: See corrections.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
8/19/2019TransferCorrect following Item  Connect outdoor unit and conduit connection plate near refrigerant line opening.  
8/19/2019TransferCorrect following Item  Indoor unit shows max OCP 15 amp. Does outdoor unit provide this supplementary protection for indoor unit? Provide documentation showing proper OCP for indoor unit.  
8/19/2019TransferCorrect following Item  Receptacle required at new ac unit. Readily accessible GFCI WR type receptacle with extra duty inuse cover.  