Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 563657
Inspection Type: Temp Electric
Inspector: M.Green
Result: Correction
Comment: 400A temp electrical service.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
7/8/2024TransferCorrect following Item  Service lateral conduit.Requires #1/0 copper bonding conductor from CT enclosure to grounding bushing.
7/8/2024TransferCorrect following Item  Gutter containing conductors supplying 50A temp receptacles.Bond at least (1) equipment ground to the gutter.