Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 559695
Inspection Type: Final Mechanical
Inspector: K.Hanson
Result: Correction
Comment: Partial Mechanical Final - Approved 2 of 3 corrections addressed, 1 correction remains regarding wall behind type 1 hood.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
4/18/2019CorrectedMechFinalSee commentsSee Inspector CommentsWall below Type 1 hoodAs per 2012 IMC 507.9 Exception a smooth, cleanable, nonabsorbent and noncombustible material shall be installed between the hood & the gypsum wallboard over an area extending not less than 18" in all directions from hood.
4/18/2019CorrectedMechFinal14Type I Exhaust Fan Drain <p>Vertical&nbsp;upblast type I hood exhaust fan shall have an approved drain outlet and grease reservoir IMC 506.5.2</p> Rooftop EF serving grease ductAttach grease catch.
4/18/2019CorrectedMechFinal13Type I Exhaust Fan HingedVertical upblast type I hood exhaust fan shall be hinged IMC 506.5.3Rooftop EF serving type 1 hoodHinge kit required.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS