| Date | Status | Code | Description | Ref | Location | Comments |
| 4/18/2019 | Transfer | MechFinal | See comments | See Inspector Comments | Wall below Type 1 hood | As per 2012 IMC 507.9 Exception a smooth, cleanable, nonabsorbent and noncombustible material shall be installed between the hood & the gypsum wallboard over an area extending not less than 18" in all directions from hood. |
| 4/18/2019 | Corrected | MechFinal14 | Type I Exhaust Fan Drain |
<p>Vertical upblast type I hood exhaust fan shall have an approved drain outlet and grease reservoir IMC 506.5.2</p>
| Rooftop EF serving grease duct | Attach grease catch. |
| 4/18/2019 | Corrected | MechFinal13 | Type I Exhaust Fan Hinged | Vertical upblast type I hood exhaust fan shall be hinged IMC 506.5.3 | Rooftop EF serving type 1 hood | Hinge kit required. |