Inspection #: 559688
Inspection Type: Final Mechanical
Inspector: K.Hanson
Result: Correction
Comment: Partial Mechanical Final - Approved 2nd layer fire wrap approved for entire grease duct, all else OK, see corrections.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
4/18/2019TransferMechFinalSee commentsSee Inspector CommentsWall below Type 1 hoodAs per 2012 IMC 507.9 Exception a smooth, cleanable, nonabsorbent and noncombustible material shall be installed between the hood & the gypsum wallboard over an area extending not less than 18" in all directions from hood.
4/18/2019CorrectedMechFinal14Type I Exhaust Fan Drain <p>Vertical&nbsp;upblast type I hood exhaust fan shall have an approved drain outlet and grease reservoir IMC 506.5.2</p> Rooftop EF serving grease ductAttach grease catch.
4/18/2019CorrectedMechFinal13Type I Exhaust Fan HingedVertical upblast type I hood exhaust fan shall be hinged IMC 506.5.3Rooftop EF serving type 1 hoodHinge kit required.