Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 558905
Inspection Type: Final Electrical
Inspector: E.Widman
Result: Correction
Comment: See corrections for area.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
4/26/2019TransferCorrect Below* 15 amp max OCP required for KEF-1.  
4/26/2019TransferCorrect Below* Heat trace at freezer unit. Provide installation instructions for type installed. Labeling required for heat trace, reference 426 for clarification. GFPE breaker required. Breaker lock required for disconnect (cord/plug not factory installed).
4/26/2019TransferCorrect Below* Proper cord connection for ice cream station required. See detail on drawings.  
4/12/2019CorrectedCorrect Below* at panelsroom numbers not adequate for circuit descriptions, provide more detail
4/12/2019TransferCorrect Below* at sales counterfinish surfaces/cabinets not complete at sales counter
4/12/2019TransferCorrect Below* kitchen equimentneed to verify listing/ratings of kitchen equipment
4/12/2019CorrectedCorrect Below* Freezer/cooler/RTUsnot complete