| Date | Status | Code | Description | Ref | Location | Comments |
| 3/8/2019 | Corrected | Correct Below | * | | Verify max overcurrent protection for roof unit is 15 amp max. | |
| 3/8/2019 | Corrected | Correct Below | * | | WR type GFCI receptacle required at roof top refrigeration equipment. | |
| 3/8/2019 | Corrected | Correct Below | * | | Verify Motor overload protection per 430.32. | |
| 3/8/2019 | Corrected | Correct Below | * | | Provide MOA stamped reviewed plans for inspection. | |