Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 553410
Inspection Type: Fire Alarm Final
Inspector: M.Warren
Result: Approved
Comment: close out permit for 4th floor. inspection before 10AM Requested by: Kathryn Tranum 907-223-4367 ktranum@atsalaska.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
7/17/2019 firealarm12Fire Alarm approved COFire Alarm approved CO  
2/20/2019CorrectedFireWalarmFinalOtherFire Alarm Final OtherPlease correct the following: <div>|| correct smoke zones (FM-1, ASF beam detector to report one zone only) || C-1 supply fan&nbsp; reporting status inputs on/off&nbsp; ||&nbsp; Fire caulk penetrations in 4th floor electrical room. &nbsp;</div><div><br></div><div>Balance of corrections carried over from other FA permits have been verified and resolved.&nbsp; I will verify resolution in the system once ATS forwards any potentially open permit numbers.</div><div><br></div><div>Atrium smoke control and evacuation system, and related components including basement beam activators, verified.</div>