Inspection #: 553239
Inspection Type: Fire Alarm Final
Inspector: C.Mondloch
Result: Correction
Comment: Hello. Per request, we are scheduling a witness test for 5 separate areas to verify smoke evacuation mode at 8:00 AM. Kathy Trannum will be there from ATS Alaska. Please call with an ETA - 907-223-4367 Requested by: Josh Olds 907-317-1633 jolds@atsalaska.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
2/20/2019TransferFireWalarmFinalOtherFire Alarm Final OtherPlease correct the following: <div>|| correct smoke zones (FM-1, ASF beam detector to report one zone only) || C-1 supply fan&nbsp; reporting status inputs on/off&nbsp; ||&nbsp; Fire caulk penetrations in 4th floor electrical room. &nbsp;</div><div><br></div><div>Balance of corrections carried over from other FA permits have been verified and resolved.&nbsp; I will verify resolution in the system once ATS forwards any potentially open permit numbers.</div><div><br></div><div>Atrium smoke control and evacuation system, and related components including basement beam activators, verified.</div>