Inspection #: 551224
Inspection Type: Electrical Rough
Inspector: M.Green
Result: Correction
Comment: JENNIFER 717-6419 OR SISTER IN LAW 782-7741 NOTES: 1. GFCIs (except at washer) and all other receptacles appear to be existing. Any replaced receptacles will need to be: *Tamper resistant. *AFCI protected or AFCI / GFCI protected per 2014 NEC. 2. Any replaced lighting fixtures will need to be suitable for 60C rated wiring. 3. May call Mike if questions, 317-6980.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
7/17/2019Transfer01See inspection comments Under trailer grounding connections to trailer frame from panel, to water line, to gas line. Cannot use self-drilling / self-tapping screws. Use through-bolt and nut. Use foot lug as terminal for wire. Scrape off rust under foot lug.
7/17/2019Transfer01See inspection comments Washer receptacle in bathroom.Needs to be GFCI / AFCI, tamper resistant type.
7/17/2019Transfer01See inspection comments Water heater compartment accessible from exterior only.Receptacle needs to be GFCI, tamper resistant type.
7/17/2019Transfer01See inspection comments Trench from electrical service to under trailer.At trailer end, make sure conductors will be 24 inches deep minimum.