| Date | Status | Code | Description | Ref | Location | Comments |
| 7/17/2019 | Transfer | 01 | See inspection comments | | Under trailer grounding connections to trailer frame from panel, to water line, to gas line. | Cannot use self-drilling / self-tapping screws. Use through-bolt and nut. Use foot lug as terminal for wire. Scrape off rust under foot lug. |
| 7/17/2019 | Transfer | 01 | See inspection comments | | Washer receptacle in bathroom. | Needs to be GFCI / AFCI, tamper resistant type. |
| 7/17/2019 | Transfer | 01 | See inspection comments | | Water heater compartment accessible from exterior only. | Receptacle needs to be GFCI, tamper resistant type. |
| 7/17/2019 | Transfer | 01 | See inspection comments | | Trench from electrical service to under trailer. | At trailer end, make sure conductors will be 24 inches deep minimum. |