Inspection #: 550266
Inspection Type: Fire Alarm Final
Inspector: C.Mondloch
Result: Correction
Comment: Hello. Per request, we are scheduling a witness test for 5 separate areas to verify smoke evacuation mode at 8:00 AM. Kathy Trannum will be there from ATS Alaska. Please call with an ETA - 907-223-4367 Requested by: Joshua Olds 907-317-1633 jolds@atsalaska.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
2/19/2019Transferfirealarm13Please correct the followingPlease correct the following: <div>C1 - no status showing reporting on/off (FM-1)</div><div><br></div><div>NOTE: Outside air dampers not opening for M1 and M3.&nbsp; This is not a fire alarm issue, but being noted here because it will need to be addressed by mechanical.</div>