Inspection #: 549329
Inspection Type: Final Electrical
Inspector:
Result:
Comment:

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
1/7/2019 Correct Below*  provide MOA stamped/approved drawings
1/7/2019 Correct Below*  VRU kiosk seal-offs must be poured
1/7/2019 Correct Below*  label panels where fed from
1/7/2019 Correct Below*  truck rack kiosks grounding electrode conductor must bond to disconnect and at all boxes/conduits it passes through
1/7/2019 Correct Below*  bond electrode at VRU kiosk transformer