Inspection #: 548048
Inspection Type: Final Electrical
Inspector: M.Green
Result: Correction
Comment: Please contact Justin 30 minutes prior to arriving at inspection Requested by: Justin Morgan 907-306-3020 info@supremeelectricak.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
12/19/2018TransferCorrect Below* Show window.Complete sign installation.
12/19/2018TransferCorrect Below* Main breaker.Need access to electrical room. Need to see correct labelling for OCPD serving this space. Mall management needs to provide a letter detailing procedure for accessing main breaker to give to tennant.
12/19/2018TransferCorrect Below* At panel.Post electrical power plan to show circuits feeding receptacles.
12/19/2018TransferCorrect Below* Floor boxes.Need trim plates for receptacles and some blank plates.