Inspection #: 544491
Inspection Type: Electrical Inspection
Inspector: M.Green
Result: Approved
Comment: Please call 1 hour Before Inspection. No tech on-site Requested by: Josh Endes 907-354-5631 bobby@vannoyelectric.com Electrical installation to serve AC units. Electrical final approved. Contractor allowed to label units as having reduced working clearances and to not be serviced hot.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
11/13/2018CorrectedCorrect following Item  Rooftop units.Do not have 110.26 working clearances due to position on mounting racks.
11/13/2018CorrectedCorrect following Item  Above ceiling grid AHUs in showroom and Exam Room 2.Do not have limitted access working clearances as per 2014 NEC 424.66 Due to flex ducts or conduit and strut, hanger rods.