Inspection #: 543668
Inspection Type: Final Electrical
Inspector: D.Rooney
Result: Correction
Comment: Corrections required

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
11/15/2018TransferCorrect Below* at two south countersinstall top/bottom screws on industrial covers for receptacles
11/15/2018TransferCorrect Below* at wall displaysreceptacle behind shelf must be accessible
11/15/2018TransferCorrect Below* at panelhandle ties installed not designed for three breakers