| 10/3/2018 | Corrected | Correct following Item | | | Post available fault current and date calculated at service. All labels must be suitable for the environement. | |
| 10/3/2018 | Corrected | Correct following Item | | | Label service for load served. Reference 507.27 for requirements. | |
| 10/3/2018 | Corrected | Correct following Item | | | What is depth of service lateral? Not visible at inspection. Reference 507.26 for minimum cover requirements. | |
| 10/3/2018 | Corrected | Correct following Item | | | Meyers hub required to have bonding jumper at service equipment (service conductors). | |
| 10/3/2018 | Corrected | Correct following Item | | | Wire connections required to be 2 hole connection. Reference 303 of ESR. | |
| 10/3/2018 | Corrected | Correct following Item | | | Service does not appear to be a test block bypass. Not permitted for application. Reference 303 of Utility Equipment service standard. | |