Inspection #: 536732
Inspection Type: Final Electrical
Inspector: E.Widman
Result: Correction
Comment: See corrections.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
9/21/2018TransferCorrect Below* At over current protection. Color code changes from line and load side of Breaker at controller.
9/21/2018TransferCorrect Below* Various locations in lower control panel. Provide wiring diagram for listed panel.Grounded conductors appear to be terminated at equipment grounding terminal. Locate to neutral terminals. Various colors of wire landed at neutral grounding terminal. Are these used as grounded conductor? Required to be proper color. Reference Article 200 of NEC.
9/21/2018TransferCorrect Below* Provide factory supplied wiring diagram for control panel.  