Inspection #: 534128
Inspection Type: Electrical Inspection
Inspector: M.Green
Result: Correction
Comment: Please call 30 Minutes Before Inspection Requested by: Jason 907-631-2034 bobby@vannoyelectric.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
11/13/2018TransferCorrect following Item  Rooftop units.Do not have 110.26 working clearances due to position on mounting racks.
11/13/2018TransferCorrect following Item  Above ceiling grid AHUs in showroom and Exam Room 2.Do not have limitted access working clearances as per 2014 NEC 424.66 Due to flex ducts or conduit and strut, hanger rods.