Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 531935
Inspection Type: Electrical Inspection
Inspector: E.Widman
Result: Correction
Comment: See corrections.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/3/2018TransferCorrect following Item  Post available fault current and date calculated at service. All labels must be suitable for the environement.  
10/3/2018TransferCorrect following Item  Label service for load served. Reference 507.27 for requirements.  
10/3/2018TransferCorrect following Item  What is depth of service lateral? Not visible at inspection. Reference 507.26 for minimum cover requirements.  
10/3/2018TransferCorrect following Item  Meyers hub required to have bonding jumper at service equipment (service conductors).  
10/3/2018TransferCorrect following Item  Wire connections required to be 2 hole connection. Reference 303 of ESR.  
10/3/2018TransferCorrect following Item  Service does not appear to be a test block bypass. Not permitted for application. Reference 303 of Utility Equipment service standard.  
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS