Inspection Type: Electrical Inspection
Inspector: D.Rooney
Result: Correction
Comment: Corrections required

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
8/6/2018TransferCorrect following Item  throughoutground wires in some boxes not properly splices - check all devices and lights
8/6/2018TransferCorrect following Item  hot dog rollerequpment is un listed and unsafe (cord not properly attached)
8/6/2018TransferCorrect following Item  at UG feederexpose conduit at both ends of run
8/6/2018TransferCorrect following Item  at outside disconnecctneutral needs to break at disconnect
8/6/2018TransferCorrect following Item  at outside disconnectchase nipple on top of disconnect needs to be sealed against water entry
8/6/2018TransferCorrect following Item  at outside disconnectliquidtight must be longer to have some slack to account for ground movement - leave off straps within 3' of earth
8/6/2018TransferCorrect following Item  at ground rodsexpose two grounds rods - GEC must go to ground bus at disconnect
8/6/2018TransferCorrect following Item  at panelno panel schedule provided - 30 amp breaker too big for heater rated 14 amps at 208 and receptacle rated 20 amps
8/6/2018TransferCorrect following Item  on plansno load calculation provided for concession stand - show load calculation for anticipated loads