| Date | Status | Code | Description | Ref | Location | Comments |
| 8/6/2018 | Transfer | Correct following Item | | | throughout | ground wires in some boxes not properly splices - check all devices and lights |
| 8/6/2018 | Transfer | Correct following Item | | | hot dog roller | equpment is un listed and unsafe (cord not properly attached) |
| 8/6/2018 | Transfer | Correct following Item | | | at UG feeder | expose conduit at both ends of run |
| 8/6/2018 | Transfer | Correct following Item | | | at outside disconnecct | neutral needs to break at disconnect |
| 8/6/2018 | Transfer | Correct following Item | | | at outside disconnect | chase nipple on top of disconnect needs to be sealed against water entry |
| 8/6/2018 | Transfer | Correct following Item | | | at outside disconnect | liquidtight must be longer to have some slack to account for ground movement - leave off straps within 3' of earth |
| 8/6/2018 | Transfer | Correct following Item | | | at ground rods | expose two grounds rods - GEC must go to ground bus at disconnect |
| 8/6/2018 | Transfer | Correct following Item | | | at panel | no panel schedule provided - 30 amp breaker too big for heater rated 14 amps at 208 and receptacle rated 20 amps |
| 8/6/2018 | Transfer | Correct following Item | | | on plans | no load calculation provided for concession stand - show load calculation for anticipated loads |