Inspection #: 524484
Inspection Type: Fire Alarm Final
Inspector: M.Warren
Result: Approved
Comment: This inspection is to verify the requited NAC devices are in installed, no audible testing is expected nor coordinated during this inspection. Onsite contact for Siemens is Earl Jones, Cell is 907-229-6096 Requested by: Earl Jones 907-229-6096

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
7/6/2018 firealarm11Fire Alarm approved CCOFire Alarm approved for CCO Fire Alarm approved for CCO till July 30, 2018
7/6/2018 firealarm13Please correct the followingPlease correct the following: (1) Speaker Strobe N12-21-06 is mounted too high (over 8 feet) to meet ADA requirements. (2) Speaker Strobe N12-22-14 is mounted too low (less than 80 inch) to meet ADA requirements. (3) extra strobe located next to Speaker Strobe N12-21-07 not shown on drawing or calculations, update drawings. (Code requirements for strobes) Wall-mounted appliances shall be mounted such that the entire lens is not less than 80 in. (2.03 m) and not greater than 96 in. (2.44 m) above the finished floor.