Inspection #: 521533
Inspection Type: Final Fire Inspection
Inspector: M.Warren
Result: Correction
Comment:

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
6/19/2018TransferFireOtherOtherCorrection(s) #1Please correct the following item(s): Advisory for spinkler obstruction in gym. Sprinkler designer to install new line at each beam and arm over under new duct due to obstruction.
6/19/2018TransferFireOtherOtherCorrection(s) #1Please correct the following item(s): Advisory inspection for incedental combustibles in concealed spaces in hall I-133. Section 8.15.1.2.1 out of NFPA 13 is applicable and no sprinkler coverage is required.