| Date | Status | Code | Description | Ref | Location | Comments |
| 8/16/2018 | Transfer | Correct Below | * | | at motor controllers | overloads in both controllers too big. bond around concentric knockouts on 480V controlleer |
| 6/7/2018 | Corrected | Correct Below | * | | Add support at exposed ceiling locations for cables at luminaires. | |
| 6/7/2018 | Corrected | Correct Below | * | | 3 locations, open boxes. | |