Inspection #: 517190
Inspection Type: Fire Alarm Final
Inspector: B.Meinhardt
Result: Partial
Comment: $570 AFTER HOURS INSPECTION FEE PAID BY WES WITH MCN CONSTRUCTION 907-982-8032. INSPECTION OKAY'D BY CLEO HILL.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
7/6/2018Transferfirealarm11Fire Alarm approved CCOFire Alarm approved for CCO Fire Alarm approved for CCO till July 30, 2018
7/6/2018Transferfirealarm13Please correct the followingPlease correct the following: (1) Speaker Strobe N12-21-06 is mounted too high (over 8 feet) to meet ADA requirements. (2) Speaker Strobe N12-22-14 is mounted too low (less than 80 inch) to meet ADA requirements. (3) extra strobe located next to Speaker Strobe N12-21-07 not shown on drawing or calculations, update drawings. (Code requirements for strobes) Wall-mounted appliances shall be mounted such that the entire lens is not less than 80 in. (2.03 m) and not greater than 96 in. (2.44 m) above the finished floor.