| Date | Status | Code | Description | Ref | Location | Comments |
| 5/17/2018 | | Fire 2 | CCO approval | Fire Final approved for CCO | | Fire final approved for furniture and fixture only, Peak Neuroloey staff is allowed in for office setup. No public occupancy or patients allowed until fire alarm issues are resolved and tested. |
| 5/17/2018 | | FireOtherOther | Correction(s) #1 | Please correct the following item(s): | | Submit change order to C18-1342, the buiding is not II-A consgtruction, it is IIB. |
| 5/17/2018 | | FireOtherOther | Correction(s) #1 | Please correct the following item(s): | | This is a Level 2 alteration per the 2012 IEBC and fire alarm is required to be code compliant in the TI area. |
| 5/17/2018 | | FireOtherOther | Correction(s) #1 | Please correct the following item(s): | | 90 minute door between suites requires door holder and mangnetic hold open device |