Inspection #: 517114
Inspection Type: Final Fire Inspection
Inspector: B.Meinhardt
Result: CondAppr
Comment: As late Pm as possible Requested by: Jim Kistler 907-232-7500 Jkistler@fwalaska.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
5/17/2018 Fire 2CCO approvalFire Final approved for CCO Fire final approved for furniture and fixture only, Peak Neuroloey staff is allowed in for office setup. No public occupancy or patients allowed until fire alarm issues are resolved and tested.
5/17/2018 FireOtherOtherCorrection(s) #1Please correct the following item(s): Submit change order to C18-1342, the buiding is not II-A consgtruction, it is IIB.
5/17/2018 FireOtherOtherCorrection(s) #1Please correct the following item(s): This is a Level 2 alteration per the 2012 IEBC and fire alarm is required to be code compliant in the TI area.
5/17/2018 FireOtherOtherCorrection(s) #1Please correct the following item(s): 90 minute door between suites requires door holder and mangnetic hold open device