Inspection #: 515300
Inspection Type: Fire Alarm Final
Inspector:
Result:
Comment:

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
5/5/2018 firealarm13Please correct the followingPlease correct the following: Need to retest the duct detectors, the fans were not shutting down.
5/5/2018 FireWalarmFinalOtherFire Alarm Final OtherPlease correct the following: Submit change order to the fire alarm palsn for approval. Orginally SLC was from west panel and now it is on the Roming panel
5/5/2018 firealarm13Please correct the followingPlease correct the following: Hall between libary and West High strobes are out of sync by double doors per 2010 NFPA 72 section 18.5.4.3.2
5/5/2018 firealarm2Install cert <p class="MsoNormal"><font face="Times New Roman">Provide Installation Certification and test report.</font></p>  Provide Fire Alarm Installers Cert
5/5/2018 firealarm6FACP mapFloor plan/map required at main entry door showing location of FACP. Provide updated fire alarm maps at West High and Roming Middle Schools
5/5/2018 firealarm11Fire Alarm approved CCOFire Alarm approved for CCO Fire Alarm approved for CCO till June 15, 2018