| 5/5/2018 | | firealarm13 | Please correct the following | Please correct the following: | | Need to retest the duct detectors, the fans were not shutting down. |
| 5/5/2018 | | FireWalarmFinalOther | Fire Alarm Final Other | Please correct the following: | | Submit change order to the fire alarm palsn for approval. Orginally SLC was from west panel and now it is on the Roming panel |
| 5/5/2018 | | firealarm13 | Please correct the following | Please correct the following: | | Hall between libary and West High strobes are out of sync by double doors per 2010 NFPA 72 section 18.5.4.3.2 |
| 5/5/2018 | | firealarm2 | Install cert |
<p class="MsoNormal"><font face="Times New Roman">Provide Installation Certification and test report.</font></p>
| | Provide Fire Alarm Installers Cert |
| 5/5/2018 | | firealarm6 | FACP map | Floor plan/map required at main entry door showing location of FACP. | | Provide updated fire alarm maps at West High and Roming Middle Schools |
| 5/5/2018 | | firealarm11 | Fire Alarm approved CCO | Fire Alarm approved for CCO | | Fire Alarm approved for CCO till June 15, 2018 |