Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 512941
Inspection Type: Final Electrical
Inspector: M.Green
Result: Approved
Comment: LATE AM 10-11 CALL WHEN COMING Requested by: JOHN 306-1071 TI electrical final approved. Dimond Center has provided a letter stating that tennant has a key for access to the electrical room where the disconnect feeding this occupancy is located.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
4/18/2018CorrectedCorrect Below* Feeder disconnect accesss.Tennant will need to demonstrate access by key or have written procedure for access.
4/18/2018CorrectedCorrect Below* TI switchgear.Label as to source of supply: Panel and disconnect number and room where feeder disconnect located.
4/18/2018CorrectedCorrect Below* TI space water line.Bond to building steel.
4/18/2018CorrectedCorrect Below* RTU-1.*Unit appears to require 25A max. OCPD. 35A installed. *Rooftop gas line and blocking need to be 3-1/2 feet from the electrical compartment access. *Label unit to show TI space it supplies and location of OCPD. Labelling to be suitable for environment.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter