Inspection Type: Final Electrical
Inspector: E.Widman
Result: Correction
Comment: If possible, please schedule for AM before 11:00 am, as I will not be onsite later in the day. Inspection is for deficiency corrections. Requested by: Chris Stafford 441-2031 chrisstafford.wiredak@gmail.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
4/3/2018CorrectedCorrect Below* Post floor plan at panels to assist in identifying circuits, or unique and specific language required. Reference 408.4. Approved degree of detail required (floor plan). Are room #'s planned to be permanently posted at individual rooms? 
4/3/2018CorrectedCorrect Below* Lighting incomplete in storage L2.  
4/3/2018CorrectedCorrect Below* Power poles incomplete at library.  
4/3/2018CorrectedCorrect Below* 15 amp max OCP for cabinet unit heaters in library and associated area.  
4/3/2018CorrectedCorrect Below* Library vestibule incomplete.  
4/2/2018CorrectedCorrect Below* Boiler roomVerify overload protection for pumps 2B and 2A.
4/2/2018CorrectedCorrect Below* Boiler room. Properly secure flex at various locations.
3/30/2018CorrectedCorrect Below* east end of corridor IMC-21ceiling not complete
3/30/2018CorrectedCorrect Below* in bathrooms IMC-19, IMC-20ceilings not complete
3/30/2018CorrectedCorrect Below* west end of corridor IMC-21Door operators not complete
3/30/2018TransferCorrect Below* in mech rooms IMC-17, IMC-47.5 hp VFDs appear to be too small for 8 hp motors in AHU1-1, AHU1-2, AHU2-1, AHU2-2