| Date | Status | Code | Description | Ref | Location | Comments |
| 4/3/2018 | Transfer | Correct Below | * | | Post floor plan at panels to assist in identifying circuits, or unique and specific language required. Reference 408.4. Approved degree of detail required (floor plan). Are room #'s planned to be permanently posted at individual rooms? | |
| 4/3/2018 | Transfer | Correct Below | * | | Lighting incomplete in storage L2. | |
| 4/3/2018 | Transfer | Correct Below | * | | Power poles incomplete at library. | |
| 4/3/2018 | Transfer | Correct Below | * | | 15 amp max OCP for cabinet unit heaters in library and associated area. | |
| 4/3/2018 | Transfer | Correct Below | * | | Library vestibule incomplete. | |
| 4/2/2018 | Transfer | Correct Below | * | | Boiler room | Verify overload protection for pumps 2B and 2A. |
| 4/2/2018 | Transfer | Correct Below | * | | Boiler room. | Properly secure flex at various locations. |
| 3/30/2018 | Transfer | Correct Below | * | | east end of corridor IMC-21 | ceiling not complete |
| 3/30/2018 | Transfer | Correct Below | * | | in bathrooms IMC-19, IMC-20 | ceilings not complete |
| 3/30/2018 | Transfer | Correct Below | * | | west end of corridor IMC-21 | Door operators not complete |
| 3/30/2018 | Transfer | Correct Below | * | | in mech rooms IMC-17, IMC-4 | 7.5 hp VFDs appear to be too small for 8 hp motors in AHU1-1, AHU1-2, AHU2-1, AHU2-2 |