Inspection #: 510378
Inspection Type: Final Electrical
Inspector: E.Widman
Result: Correction
Comment: See correction for progress final for mechanical/boiler room.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
4/2/2018TransferCorrect Below* Boiler roomVerify overload protection for pumps 2B and 2A.
4/2/2018TransferCorrect Below* Boiler room. Properly secure flex at various locations.
3/30/2018TransferCorrect Below* east end of corridor IMC-21ceiling not complete
3/30/2018TransferCorrect Below* in bathrooms IMC-19, IMC-20ceilings not complete
3/30/2018TransferCorrect Below* west end of corridor IMC-21Door operators not complete
3/30/2018TransferCorrect Below* in mech rooms IMC-17, IMC-47.5 hp VFDs appear to be too small for 8 hp motors in AHU1-1, AHU1-2, AHU2-1, AHU2-2