| Date | Status | Code | Description | Ref | Location | Comments |
| 4/2/2018 | Transfer | Correct Below | * | | Boiler room | Verify overload protection for pumps 2B and 2A. |
| 4/2/2018 | Transfer | Correct Below | * | | Boiler room. | Properly secure flex at various locations. |
| 3/30/2018 | Transfer | Correct Below | * | | east end of corridor IMC-21 | ceiling not complete |
| 3/30/2018 | Transfer | Correct Below | * | | in bathrooms IMC-19, IMC-20 | ceilings not complete |
| 3/30/2018 | Transfer | Correct Below | * | | west end of corridor IMC-21 | Door operators not complete |
| 3/30/2018 | Transfer | Correct Below | * | | in mech rooms IMC-17, IMC-4 | 7.5 hp VFDs appear to be too small for 8 hp motors in AHU1-1, AHU1-2, AHU2-1, AHU2-2 |