| Date | Status | Code | Description | Ref | Location | Comments |
| 3/30/2018 | Transfer | Correct Below | * | | east end of corridor IMC-21 | ceiling not complete |
| 3/30/2018 | Transfer | Correct Below | * | | in bathrooms IMC-19, IMC-20 | ceilings not complete |
| 3/30/2018 | Transfer | Correct Below | * | | west end of corridor IMC-21 | Door operators not complete |
| 3/30/2018 | Transfer | Correct Below | * | | in mech rooms IMC-17, IMC-4 | 7.5 hp VFDs appear to be too small for 8 hp motors in AHU1-1, AHU1-2, AHU2-1, AHU2-2 |
| 1/30/2018 | Corrected | 01 | See inspection comments | | Library court soffits. | Securely fasten cables within 12" of termination. |