Inspection #: 509875
Inspection Type: Final Electrical
Inspector: D.Rooney
Result: Partial
Comment: inspected area SW of library except boiler room IMC-16 - electrical final approved except as noted

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
3/30/2018TransferCorrect Below* east end of corridor IMC-21ceiling not complete
3/30/2018TransferCorrect Below* in bathrooms IMC-19, IMC-20ceilings not complete
3/30/2018TransferCorrect Below* west end of corridor IMC-21Door operators not complete
3/30/2018TransferCorrect Below* in mech rooms IMC-17, IMC-47.5 hp VFDs appear to be too small for 8 hp motors in AHU1-1, AHU1-2, AHU2-1, AHU2-2
1/30/2018Corrected01See inspection comments Library court soffits. Securely fasten cables within 12" of termination.