Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 506757
Inspection Type: Final Electrical
Inspector: M.Green
Result: Correction
Comment: Am inspection please call Ryan when on site 229-9527 Requested by: Ryan Maidl 229-9527 ryan@necak.com Most items from previous inspections resolved. Only those below remain.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
3/6/2018TransferCorrect Below* Electrical panels.(2) nominal voltage systems in building require color code to be posted.
3/6/2018TransferCorrect Below* Interior sign circuits.Need breaker locks.
3/6/2018TransferCorrect Below* Rooftop walk-in cooler / freezer condensor.Platform to eleiminate gas line violation of 110.26 working clearances does not permit opening of electrical compartment.
3/6/2018TransferCorrect Below* Rooftop RTU-11, RTU-12.Ductwork under electrical compartment violates 110.26 working clearances. Electrical compartment doors do not open 90 degrees.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter