Date | Status | Code | Description | Ref | Location | Comments |
3/6/2018 | Transfer | Correct Below | * | | Electrical panels. | (2) nominal voltage systems in building require color code to be posted. |
3/6/2018 | Transfer | Correct Below | * | | Interior sign circuits. | Need breaker locks. |
3/6/2018 | Transfer | Correct Below | * | | Rooftop walk-in cooler / freezer condensor. | Platform to eleiminate gas line violation of 110.26 working clearances does not permit opening of electrical compartment. |
3/6/2018 | Transfer | Correct Below | * | | Rooftop RTU-11, RTU-12. | Ductwork under electrical compartment violates 110.26 working clearances. Electrical compartment doors do not open 90 degrees. |