Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 506082
Inspection Type: Hood and Duct Fire System Final
Inspector: M.Warren
Result: Correction
Comment: Requested by: Tyrel Laret 907-350-4930 Tlaret@yukonfire.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
2/21/2018TransferHoodDuctFASee Comments  (1) provide a sign at the manuel set relay on the gas line. (2) Install a relay for conductors to the hood suppresion so line integrity is possible. (3) Nozzle placement at the griddle at the main line hood needs adjustmant. (3) Complete tank and actuator at hood 3. (4) Provide nozzle caps at hood 3. (5) Need to check for auto shut down for supply air and auto fan start up upon heat rise.
2/21/2018TransferHoodDuctFASee Comments  Inspection under this permit was made to all three hoods.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS