Inspection #: 506072
Inspection Type: Final Fire Inspection
Inspector: M.Warren
Result: NoResult
Comment: Please call and will meet on site Requested by: Mike Swiantek 907-727-1496 Mike@mcnconstruction.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
3/5/2018TransferFire 13Correction(s) #1Please correct the following: Provide a You are Here map at both the north first floor and south east second floor entrances for the location of the sprinkler riser room and fire alarm panel.
3/5/2018TransferFire 13Correction(s) #1Please correct the following: Final evaluation of emergency lights and exit signs will be made after games are in place.
3/5/2018TransferFire 13Correction(s) #1Please correct the following: Complete the fire extinguisher installation per the walk through on 2/5/2018.
3/5/2018TransferFire 13Correction(s) #1Please correct the following: Install a knox on the north entrance on the split face block with a sign on it that states D & B knox. This is done due to no solid material to mount to on the phenolic panels at the doors.
3/5/2018TransferFire 13Correction(s) #1Please correct the following: Install sprinkler room signs and have occupancy placards per plan with an additional over all occupancy sign at the mall entrance on the 2nd floor.
3/5/2018TransferFire 13Correction(s) #1Please correct the following: Complete the fire alarm system and the last comment on the sprinkler system on lack of residual pressure.
3/5/2018TransferFire 2CCO approvalFire Final approved for CCO Emergency lighting operation needs to be resolved when the fire alarm system operates or a power outage and the games shut down that provide ambiant lighting. Emergency lighting needs to stay operational until the games provide the code required minimum lighting level of 1 foot candle average on the walking egress surface.